ACM-LV Series 20–160kVA Modular UPS

Product Overview

ACwatt ACM-LV Series 20–160kVA Modular UPS is a three-phase online double-conversion UPS for 200/208/220V power systems in server rooms, enterprise IT facilities and campus data centers.

Compact modular design: Each 20kW power module occupies 2U. Cabinet ratings of 60, 100 and 160kVA support different capacity requirements, with an output power factor of 1.0.

Power quality: Input power factor exceeds 0.99, input THDi is below 3%, and output voltage accuracy is ±1%. Efficiency reaches up to 94%.

Backup configuration: Selectable battery quantities support different system configurations. An optional 30A charger module is available for long-backup applications.

Monitoring: The 60/100kVA models feature a 7-inch touch LCD; the 160kVA model uses a 10-inch touch LCD. USB, RS232, RS485 and dry contacts are standard.

Installed capacity depends on module quantity and cabinet rating. Mounting arrangement, battery configuration and backup time depend on the selected model and project requirements.

Applications

Broadcasting

Broadcasting

Education

Education

Enterprise IT

Enterprise IT

Server Rooms

Server Rooms

Data Parameters

ACM-LV Series 20–160kVA Modular UPS — Technical Specifications
ModelAC60/20-LVAC100/20-LVAC160/20-LV
Rated Power60kVA/60kW100kVA/100kW160kVA/160kW
Power Module20kW, 2U
InputWiring3P5W (3P + N + PE)
Rated Voltage200/208/220VAC (L-L)
Frequency50/60Hz; input range: 40–70Hz
Power Factor>0.99
Current DistortionTHDi <3%
Voltage Range167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50%
BatteryRated Voltage±120VDC with default 20 batteries; 20–24 batteries selectable
ChargingMaximum charging capacity: 20% of Pout; accuracy: ±1%
BypassRated Voltage200/208/220VAC (L-L)
Voltage WindowAdjustable: −40% to +25%; default: −20% to +15%
OutputVoltage / Frequency200/208/220VAC (L-L), 50/60Hz
Power Factor1.0
Voltage Accuracy±1.0%
Voltage DistortionTHDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3
Inverter Overload110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms
SystemEfficiencyUp to 94%
DisplayLED + 7-inch touch LCDLED + 10-inch touch LCD
Standard FeaturesUSB, RS232, RS485, dry contacts, cold start
OptionsSNMP card, AS400 card, parallel kit, air filter, bottom entry kit
ProtectionIP20
EnvironmentOperating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing
Dimensions
(W × D × H)
Cabinet482 × 816 × 796mm
18U, excluding wheels
482 × 816 × 1018mm
23U, excluding wheels
600 × 1000 × 2000mm
Module440 × 678 × 85mm (2U)
WeightCabinet113kg132kg260kg
Module23kg