ACM-HV Series 100–1200kVA Modular UPS

Product Overview

ACwatt ACM-HV Series 100–1200kVA Modular UPS is a three-phase online double-conversion UPS for 440/480V power systems in data centers and critical infrastructure.

Modular capacity: Built around 100kW power modules, with cabinet ratings of 400, 500, 600, 800 and 1200kVA and an output power factor of 1.0.

Power quality: Efficiency reaches up to 97.3%, with input power factor >0.99 and input THDi <2% at 100% linear load.

Battery options: MOD100E-HV supports a three-wire ±240VDC battery connection; MOD100E-HV-Li supports a two-wire 480VDC connection without a battery neutral.

Monitoring and integration: A 10-inch touch LCD provides local monitoring. USB, RS232, RS485 and dry contacts are standard, with optional SNMP and AS400 cards.

Installed capacity depends on module quantity and cabinet rating. Battery configuration and backup time depend on the selected module version, battery system and load.

Applications

Healthcare

Healthcare

Energy

Energy

Transportation

Transportation

Finance

Finance

Data Center

Data Center

Data Parameters

ACM-HV Series 100–1200kVA Modular UPS — Technical Specifications
ModelAC400/100E-HVAC500/100E-HVAC600/100E-HVAC800/100E-HVAC1200/100E-HV
Rated Power400kVA500kVA600kVA800kVA1200kVA
Power Module Capacity100kW
InputWiring3P5W (3P + N + PE)
Rated Voltage440/480VAC (L-L)
Frequency50/60Hz; input range: 40–70Hz
Power Factor>0.99
Current DistortionTHDi <2% at 100% linear load
Voltage Range384–528VAC at full load; from 384V down to 228V, power derates from 100% to 50%
BatteryRated VoltageMOD100E-HV: ±240VDC, three-wire
MOD100E-HV-Li: 480VDC, two-wire
ChargingCharging capacity: 15% of Pout; accuracy: ±1%
BypassRated Voltage440/480VAC (L-L)
Voltage WindowAdjustable: −40% to +25%; default: −20% to +15%
OutputVoltage / Frequency440/480VAC (L-L), 50/60Hz
Power Factor1.0
Voltage Accuracy±1.0%
Voltage DistortionTHDu <1% for linear load; <3% for nonlinear load according to IEC 62040-3
Inverter Overload110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms
SystemEfficiencyUp to 97.3%
DisplayLED + 10-inch touch LCD
Standard FeaturesUSB, RS232, RS485, dry contacts, cold start, air filter
OptionsSNMP card, AS400 card, parallel kit, SPD
ProtectionIP20
EnvironmentOperating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing
Dimensions
(W × D × H)
Cabinet600 × 1000 × 2000mm800 × 1000 × 2000mm1200 × 1100 × 2000mm
Module475 × 705 × 140mm
WeightCabinet350kg380kg390kg624kg
Module47kg