ACwatt ACM-LV Series 20–100kVA Modular UPS with Internal Batteries provides three-phase online double-conversion power protection for 200/208/220V systems in server rooms, enterprise IT facilities and campus data centers.
Integrated battery configuration: Supports internal 12V 7/9Ah batteries in modular battery strips. Optional full-metal battery strips allow configurations of up to 24 strips.
Modular power: Uses 20kW power modules in a 2U format, with 60kVA and 100kVA cabinet options and an output power factor of 1.0.
Power quality: Efficiency reaches up to 94%, input power factor exceeds 0.99, and input THDi is below 3%. Output voltage accuracy is ±1%.
Operation and monitoring: A 10-inch touch LCD provides local monitoring. Maintenance bypass and a battery breaker are included, alongside USB, RS232, RS485 and dry-contact communication.
Installed power depends on module quantity and cabinet rating. Battery strip quantity, battery capacity and connected load determine backup time. Battery supply and configuration are subject to the selected package.




| Model | AC060B/20-LV-240P | AC100B/20-LV-240P | |
|---|---|---|---|
| Rated Power | 60kVA | 100kVA | |
| Power Module Capacity | 20kW | ||
| Input | Wiring | 3P5W (3P + N + PE) | |
| Rated Voltage | 200/208/220VAC (L-L) | ||
| Frequency | 50/60Hz; input range: 40–70Hz | ||
| Power Factor | >0.99 | ||
| Current Distortion | THDi <3% | ||
| Voltage Range | 167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50% | ||
| Battery | Rated DC Voltage | ±120VDC | |
| Internal Batteries | 12VDC, 7/9Ah batteries in modular battery strips | ||
| Battery Strip Configuration | Up to 24 strips; full-metal battery strips optional | ||
| Charging | Maximum charging capacity: 20% of Pout; accuracy: ±1% | ||
| Bypass | Rated Voltage | 200/208/220VAC (L-L) | |
| Voltage Window | Adjustable: −40% to +25%; default: −20% to +15% | ||
| Frequency | 50/60Hz; selectable window: ±1Hz, ±3Hz or ±5Hz | ||
| Output | Voltage / Frequency | 200/208/220VAC (L-L), 50/60Hz | |
| Power Factor | 1.0 | ||
| Voltage Accuracy | ±1.0% | ||
| Voltage Distortion | THDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3 | ||
| Inverter Overload | 110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms | ||
| Frequency Accuracy | 0.1% | ||
| System | Efficiency | Up to 94% | |
| Display | LED + 10-inch touch LCD | ||
| Standard Interfaces | USB, RS232, RS485, dry contacts | ||
| Standard Features | Air filter, maintenance bypass, battery breaker | ||
| Options | SNMP card, AS400 card, parallel kit, cold start | ||
| Protection | IP20 | ||
| Environment | Operating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing | ||
| Dimensions (W × D × H) | Cabinet | 600 × 1000 × 2000mm | |
| Power Module | 440 × 678 × 86mm (2U) | ||
| Weight | Cabinet Without Batteries | 260kg | 280kg |
| Power Module | 23kg | ||