Home > Products > UPS > 480 / 208V > Modular UPS > ACM-LV Series 10–90kVA Rack Modular UPS

ACM-LV Series 10–90kVA Rack Modular UPS

Product Overview

ACwatt ACM-LV Series 10–90kVA Rack Modular UPS is a three-phase online double-conversion UPS for 208/220V power systems in edge data centers, branch server rooms and network equipment rooms.

Compact modular design: Each 20kVA/20kW power module occupies 2U. The system supports 19-inch rack or standalone installation, with rated configurations of 20, 60, 80 and 100kVA.

Efficient power protection: Normal-mode efficiency reaches up to 95.2%, with output power factor 1.0, input power factor >0.99 and input THDi ≤2.5%.

Battery flexibility: Supports lithium battery connection and enhanced charging for high-capacity battery systems. Available charging power depends on the connected load and configuration.

Monitoring and communication: A 7- or 10-inch touch LCD is available depending on configuration. USB, RS232, RS485 and dry contacts are standard, with optional SNMP and AS400 cards.

Rated capacity and redundancy depend on the selected cabinet and module arrangement. Battery compatibility, charging settings and backup time must be matched to the project requirements.

Applications

Education

Education

Branch IT

Branch IT

Networking

Networking

Edge IT

Edge IT

Data Parameters

ACM-LV Series 10–100kVA Rack Modular UPS — Technical Specifications
Cabinet2 Slots4 Slots6 Slots2 Slots4 Slots6 Slots
Module Rated Power10kVA/10kW20kVA/20kW
Compatible CabinetAC020/10E-LVAC040/10E-LVAC060/10E-LVAC020/20E-LV
(1+1)
AC060/20E-LV
(3+1)
AC80/20E-LV
(4+2)
AC100/20E-LV
(5+1)
Cabinet Rated Power20kVA/20kW40kVA/40kW60kVA/60kW20kVA/20kW60kVA/60kW80kVA/80kW100kVA/100kW
InputWiring3P + N + PE
Rated Voltage208/220VAC (L-L)
Power Factor>0.99
Current DistortionTHDi ≤2.5%
Voltage Range167–260VAC (L-L) at full load;
from 167V down to 125V, power derates from 100% to 50%
177–260VAC (L-L) at full load;
from 177V down to 125V, power derates from 100% to 50%
Frequency Range40–70Hz
BatteryRated Voltage±120VDC; 20–24 batteries selectable
Maximum Charging Capacity50% of Pout;
20% of Pout at 100% load
50% of Pout;
10% of Pout at 100% load
InverterRated Voltage208/220VAC (L-L)
Rated Frequency50/60Hz
Output Power Factor1.0
Voltage Accuracy±1.0%
Output THDu<1% for linear load; <5.5% for nonlinear load according to IEC 62040-3
Overload110%: 1 hour;
125%: 10 minutes;
150%: 1 minute;
>150%: 200ms
≤30°C: 110% for 1 hour; 125% for 10 minutes; 150% for 1 minute; >150% for 200ms
Above 30°C to 40°C: 110% for 10 minutes; 125% for 1 minute; 150% for 5 seconds
Frequency Accuracy0.001
Synchronization WindowAdjustable: ±0.5Hz to ±5Hz; default: ±3Hz
Slew RateAdjustable: 0.5–3Hz/s; default: 0.5Hz/s
Crest Factor3:1
Phase Accuracy120° ±0.5°
BypassRated Voltage208/220VAC (L-L)
Voltage WindowAdjustable: −40% to +25%; default: −20% to +15%
Frequency WindowSelectable: ±1Hz, ±3Hz or ±5Hz
Overload110%: continuous operation;
110% < load <125%: 10 minutes;
125% < load <150%: 1 minute
SystemNormal-Mode EfficiencyUp to 94.5%Up to 95.2%
DisplayLED + 7- or 10-inch touch LCD
Safety Standards*IEC 62040-1, IEC 60950-1
EMC Standards*IEC 62040-2; IEC 61000-4-2 (ESD); IEC 61000-4-3 (RS); IEC 61000-4-4 (EFT); IEC 61000-4-5 (Surge)
ProtectionIP20
Noise at 1 Meter64dB at 100% load; 62dB at 55% load
Operating Temperature0–40°C
Humidity0–95%, non-condensing
Standard FeaturesUSB, RS232, RS485, dry contacts, cold start, air filter
OptionsSNMP card, AS400 card, SPD, parallel kit
Power ModuleDimensions
(W × D × H)
400 × 495 × 86mm
Net Weight13.1kg14.45kg
CabinetBody Dimensions
(W × D × H)
442 × 711 × 307mm
(7U)
442 × 661 × 704mm
(16U)
442 × 661 × 906mm
(20U)
442 × 711 × 307mm
(7U)
442 × 661 × 704mm
(16U)
442 × 661 × 906mm
(20U)
Maximum Dimensions
(W × D × H)
442 × 751 × 397mm442 × 840 × 796mm442 × 840 × 976mm442 × 751 × 397mm442 × 840 × 796mm442 × 840 × 976mm
Net Weight
Without Modules
50.1kg93kg101.5kg50.1kg93kg101.5kg

*Standards listed in the product catalog. Configuration and specifications are subject to the confirmed technical documentation.