Home > Products > UPS > 380V > Single phase UPS > ACS-Li Series 1~3kVA Online Tower UPS

ACS-Li Series 1~3kVA Online Tower UPS

Product Overview

ACS-Li Series 1–3kVA Online Tower UPS is a lithium-battery online UPS designed to provide continuously regulated sine-wave power with compact battery integration and intelligent battery communication.

Lithium battery platform: The series covers 1–3kVA with internal lithium-battery standard models and external-battery long-backup configurations.

Full active power: Output power factor of 1.0 allows full kW output across the rated capacity range.

Dual AC voltage platforms: Depending on model, output voltage options include 100–125Vac or 200–240Vac.

BMS-ready monitoring: RS232, optional USB/SNMP, intelligent slot, EPO, Modbus/RTU settings and RS485 BMS communication support lithium-battery monitoring.

Final configuration depends on AC voltage platform, capacity, internal or external lithium battery design, battery voltage, BMS protocol, runtime and project requirements.

Applications

Government

Government

Finance

Finance

Broadcasting

Broadcasting

Medical

Medical

Energy

Energy

Data Parameters

ACS-Li Series 1–3kVA Online Tower UPS

Technical Specifications

Rated Capacity
1–3kVA
Online double conversion
Output Power Factor
1.0
Full active power output
Form Factor
Tower
Flexible installation
Battery Platform
Lithium
BMS-ready
Product Configuration
Rated Capacity1 / 2 / 3kVA
Backup OptionsStandard internal lithium battery or long-backup external lithium battery
Output Power Factor1.0
Tower InstallationSupported; rack-tower chassis can also be installed vertically using support bases
Mechanical DimensionsExact tower dimensions are not specified in the uploaded lithium UPS manual and should be confirmed by model drawing
AC Input
Input PhaseSingle phase
AC Voltage Platforms55–155 Vac or 110–288 Vac, depending on selected model
Full-Load Input Range90–155 Vac or 176–288 Vac, depending on selected model
Rated Frequency50 / 60 Hz
Input Power Factor>0.99 at full load
AC Output
Rated Capacity1 / 2 / 3kVA
Output Voltage Options100 / 110 / 115 / 120 / 125 Vac or 200 / 208 / 220 / 230 / 240 Vac, depending on model
Output Power Factor1.0
Voltage Regulation±1%
Frequency Tolerance±0.5% of nominal
Output DistortionTHD<2% at full linear load; <5% at full non-linear load
Overload Capability102–110% for 30 min; 110–125% for 10 min; 125–150% for 30 s
Crest Factor3:1 maximum
Lithium Battery and Charger
Battery PlatformInternal lithium battery for standard models; external lithium battery for long-backup models
1kVA Battery Voltage25.6 / 38.4 Vdc standard; 25.6 Vdc long-backup
2kVA Battery Voltage76.8 Vdc standard; 51.2 Vdc long-backup
3kVA Battery Voltage76.8 / 102.4 Vdc standard; 76.8 Vdc long-backup
Standard Charger4A
Long-Backup ChargerAdjustable 1–12A
BMS CommunicationRS485 BMS communication supported when configured
Monitoring and Communication
DisplayLCD with input, output, battery, load, temperature and alarm information
Standard CommunicationRS232 and EPO
Optional CommunicationUSB, intelligent slot, SNMP and dry contacts
ProtocolsModbus / RTU / BMS settings available through the communication menu
Operating ModesNormal, bypass, battery and ECO modes
Environment and Standards
Operating Temperature0–40°C
Relative Humidity<95%, non-condensing
Operating AltitudeBelow 1000 m without derating
Storage Temperature-20–70°C
Protection LevelIP20
NoiseApproximately 45 dB at 1kVA and 50 dB at 2–3kVA
StandardsIEC/EN 62040-1, IEC/EN 62040-2 Class C2, IEC/EN 62040-3
Configuration Note: The lithium manual supports both 100–125Vac and 200–240Vac AC platforms. Confirm the selected voltage platform, lithium battery voltage, BMS protocol and final tower dimensions before publishing model-specific specifications.