Home > Products > UPS > 380V > Modular UPS > ACMG 30–150kVA Regenerative Industrial Modular UPS

ACMG 30–150kVA Regenerative Industrial Modular UPS

Product Overview

ACMG Series 30–150kVA Regenerative Industrial Modular UPS is an online double-conversion UPS designed for industrial applications with regenerative loads.

Industrial load support: Suitable for regenerative loads such as electric motors, machine tools and elevators.
Reliable operation: Features a fully isolated air duct design and IP42 protection for industrial environments.
Easy maintenance: Front-access maintenance supports convenient installation, including wall-mount installation.
Smart operation: A 10-inch touch LCD provides IoT functions for system monitoring.
Flexible input options: Optional I/O isolation transformer supports 3-wire input without neutral.

Applications

Motors

Motors

Manufacturing

Manufacturing

Elevators

Elevators

Machining

Machining

Automation

Automation

Data Parameters

ACMG 150/30 UPS Technical Specifications
ModelACMG 150/30
Rate Power150kVA
Main inputInput3P5W (3P+N+PE)
Rate Voltage380/400/415/440/480VAC (L-L)
Rate Freq.50/60Hz
Input PF>0.99
Current distortionTHDi<2%
Voltage range304 ~ 552VAC (L-L) full load; 304 ~ 171VAC (L-L) power derate from 100% to 50%
Freq. range40-70Hz
BatteryVoltage range±180 ~ ±300VDC (30-50pcs, setted)
Charging capacityMax. 20%*Pout
BypassRate voltage380/400/415/440/480VAC (L-L)
Voltage rangeRange: -40% ~ +25%, Settable, default -20% ~ +15%
Frequency range50/60Hz
InverterRate voltage380/400/415/440/480VAC (L-L)
Rate Freq.50/60Hz
Output PF1
Voltage accuracy±1.0%
Output THDu<1% (linear load); <5% (non-linear load according to IEC 62040-3)
Overload110%, 1 hour; 125%, 30 mins; 150%, 10 min; >150%, 200ms
Frequency accuracy0.1%
Synchronize windowSettable, ±0.5Hz-±5Hz, default ±3Hz
Slew rateSettable, 0.5Hz/S-3Hz/S, default 0.5Hz/S
Crest factor3:1
Phase Accuracy120°±0.5°
SystemEfficiencyUp to 96%
DisplayLED + 10 inch touch LCD
Certification- SafetyIEC62040-1, IEC60950-1
Certification- EMSIEC62040-2; IEC61000-4-2 (ESD); IEC61000-4-3 (RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge)
ConfigurationUSB, RS232, RS485, Dry contact, Air filter, Cold start, SPD
OptionSNMP card, AS400 card, Parallel kit, APP/FMI/Blue tooth
Environment-20-50℃ (operation); -25℃~70℃ (storage); 0-95% (humidity, non-condensing)
IP degreeIP42
Noise(dB,1 meter)60dB @ 100% load, 55dB @ 45% load
DimensionCabinet (W*D*H) mm600*900*2200
Module (W*D*H) mm440*475*140
Weight(kg)Cabinet340
Module30