Home > Products > UPS > 380V > Three phase UPS > ACT-LV Series 10–40kVA 208V Tower UPS — 20/40/80 Battery Options

ACT-LV Series 10–40kVA 208V Tower UPS — 20/40/80 Battery Options

Product Overview

ACwatt ACT-LV Series 10–40kVA Tower UPS provides three-phase online double-conversion protection for 200/208/220VAC line-to-line systems in server rooms, branch IT facilities and campus networks.

Model-specific battery options: Internal-battery versions use 12V/9Ah batteries. The 10kVA models offer 20, 40 or 80 batteries; 20kVA models offer 40 or 80; 30/40kVA models use 80.

Rated output: Available in 10, 20, 30 and 40kVA ratings with output power factor 1.0, ±1% voltage accuracy and input power factor >0.99.

Operation and monitoring: A 7-inch touch LCD supports local monitoring. USB, RS232, RS485 and dry contacts are standard, with optional SNMP and AS400 cards.

Installation flexibility: External-battery versions are also available. The series includes mains input/output, bypass, maintenance bypass and battery breaker configurations.

Battery quantity refers to the selected internal-battery model. Backup time depends on load and battery condition. Cabinet dimensions and weight vary by configuration.

Applications

Broadcasting

Broadcasting

Campus Networks

Campus Networks

Branch IT

Branch IT

Server Rooms

Server Rooms

Data Parameters

ACT-LV 208V Tower UPS — Internal-Battery Configurations
ModelRated PowerInternal BatteriesDimensions
W × D × H
Weight*
TT010EB-LV-2010kVA20 × 12V/9Ah250 × 645 × 556mm90kg
TT010EB-LV-4040 × 12V/9Ah250 × 694 × 724mm139kg
TT010EB-LV-8080 × 12V/9Ah400 × 770 × 854mm245kg
TT020EB-LV-4020kVA40 × 12V/9Ah250 × 694 × 724mm140kg
TT020EB-LV-8080 × 12V/9Ah400 × 770 × 854mm248kg
TT030B-LV-8030kVA80 × 12V/9Ah350 × 823 × 1200mm259kg*
TT040B-LV-8040kVA80 × 12V/9Ah286kg*

*The catalog lists 10/20kVA weights including batteries and 30/40kVA weights excluding batteries.

Electrical Specifications and External-Battery Options
Rated Power10kVA20kVA30kVA40kVA
InputWiring3P5W (3P + N + PE)
Rated Voltage200/208/220VAC (L-L)
Frequency50/60Hz; input range: 40–70Hz
Power Factor>0.99
Current DistortionTHDi <2.2%THDi <3%
Voltage Range167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50%
BatteryRated DC Voltage±120VDC
Internal-Version ChargingMaximum 50% of Pout50% of Pout
External-Version ChargingMaximum 50% of PoutMaximum 20% of Pout
Charging Accuracy±1%
BypassRated Voltage200/208/220VAC (L-L)
Voltage WindowAdjustable: −40% to +25%; default: −20% to +15%
OutputVoltage / Frequency200/208/220VAC (L-L), 50/60Hz
Power Factor1.0
Voltage Accuracy±1.0%
Voltage DistortionTHDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3
Inverter Overload110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms
SystemEfficiencyUp to 94.5%Up to 95.5%Up to 94%
DisplayLED + 7-inch touch LCD
Standard FeaturesUSB, RS232, RS485, dry contacts, air filter, cold start, EthernetUSB, RS232, RS485, dry contacts, air filter
OptionsSNMP card, AS400 card, parallel kitSNMP card, AS400 card, parallel kit, cold start
EnvironmentOperating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing
External-Battery VersionModelTT010EL-LVTT020EL-LVTT030L-LVTT040L-LV
Battery Configuration20 batteries by default; 20–24 selectable, depending on the battery system
Dimensions
(W × D × H)
250 × 745 × 556mm250 × 782 × 650mm
Weight30.8kg31.8kg66kg72kg