ACwatt ACT-LV Series 10–40kVA Tower UPS provides three-phase online double-conversion protection for 200/208/220VAC line-to-line systems in server rooms, branch IT facilities and campus networks.
Model-specific battery options: Internal-battery versions use 12V/9Ah batteries. The 10kVA models offer 20, 40 or 80 batteries; 20kVA models offer 40 or 80; 30/40kVA models use 80.
Rated output: Available in 10, 20, 30 and 40kVA ratings with output power factor 1.0, ±1% voltage accuracy and input power factor >0.99.
Operation and monitoring: A 7-inch touch LCD supports local monitoring. USB, RS232, RS485 and dry contacts are standard, with optional SNMP and AS400 cards.
Installation flexibility: External-battery versions are also available. The series includes mains input/output, bypass, maintenance bypass and battery breaker configurations.
Battery quantity refers to the selected internal-battery model. Backup time depends on load and battery condition. Cabinet dimensions and weight vary by configuration.




| Model | Rated Power | Internal Batteries | Dimensions W × D × H | Weight* |
|---|---|---|---|---|
| TT010EB-LV-20 | 10kVA | 20 × 12V/9Ah | 250 × 645 × 556mm | 90kg |
| TT010EB-LV-40 | 40 × 12V/9Ah | 250 × 694 × 724mm | 139kg | |
| TT010EB-LV-80 | 80 × 12V/9Ah | 400 × 770 × 854mm | 245kg | |
| TT020EB-LV-40 | 20kVA | 40 × 12V/9Ah | 250 × 694 × 724mm | 140kg |
| TT020EB-LV-80 | 80 × 12V/9Ah | 400 × 770 × 854mm | 248kg | |
| TT030B-LV-80 | 30kVA | 80 × 12V/9Ah | 350 × 823 × 1200mm | 259kg* |
| TT040B-LV-80 | 40kVA | 80 × 12V/9Ah | 286kg* |
*The catalog lists 10/20kVA weights including batteries and 30/40kVA weights excluding batteries.
| Rated Power | 10kVA | 20kVA | 30kVA | 40kVA | |
|---|---|---|---|---|---|
| Input | Wiring | 3P5W (3P + N + PE) | |||
| Rated Voltage | 200/208/220VAC (L-L) | ||||
| Frequency | 50/60Hz; input range: 40–70Hz | ||||
| Power Factor | >0.99 | ||||
| Current Distortion | THDi <2.2% | THDi <3% | |||
| Voltage Range | 167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50% | ||||
| Battery | Rated DC Voltage | ±120VDC | |||
| Internal-Version Charging | Maximum 50% of Pout | 50% of Pout | |||
| External-Version Charging | Maximum 50% of Pout | Maximum 20% of Pout | |||
| Charging Accuracy | ±1% | ||||
| Bypass | Rated Voltage | 200/208/220VAC (L-L) | |||
| Voltage Window | Adjustable: −40% to +25%; default: −20% to +15% | ||||
| Output | Voltage / Frequency | 200/208/220VAC (L-L), 50/60Hz | |||
| Power Factor | 1.0 | ||||
| Voltage Accuracy | ±1.0% | ||||
| Voltage Distortion | THDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3 | ||||
| Inverter Overload | 110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms | ||||
| System | Efficiency | Up to 94.5% | Up to 95.5% | Up to 94% | |
| Display | LED + 7-inch touch LCD | ||||
| Standard Features | USB, RS232, RS485, dry contacts, air filter, cold start, Ethernet | USB, RS232, RS485, dry contacts, air filter | |||
| Options | SNMP card, AS400 card, parallel kit | SNMP card, AS400 card, parallel kit, cold start | |||
| Environment | Operating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing | ||||
| External-Battery Version | Model | TT010EL-LV | TT020EL-LV | TT030L-LV | TT040L-LV |
| Battery Configuration | 20 batteries by default; 20–24 selectable, depending on the battery system | ||||
| Dimensions (W × D × H) | 250 × 745 × 556mm | 250 × 782 × 650mm | |||
| Weight | 30.8kg | 31.8kg | 66kg | 72kg | |