1P/1P, online double conversion Characteristics 1~3kVA
1P/1P, online double conversion Characteristics 1~3kVA








| Rate Power | 1kVA/1kW | 2kVA/2kW | 3kVA/3kW | ||
| Cold start | Default output 50/60Hz | ||||
| Input voltage range | 110~300VAC;100% load@176VAC~27 6VAC , 100%~50% power derating@110VAC~176VAC , 50% load@276VAC~300VAC | ||||
| Input power factor | ≥0.99 | ||||
| Frequency range | 50/60±5Hz(default), ±3Hz(s ettable) | ||||
| Output power factor | 1.0 | ||||
| Rate voltage Load response Output Recovery time Output THDu Socket(option) | 208VAC/220VAC/230VAC/ 240VAC | ||||
| ≤5% (0% - 100% -0%) | |||||
| ≤40ms (0% - 100% -0%) | |||||
| ≤2% , Linear load ; ≤ 5% non-linear load accordi ng to IEC62040-3 | |||||
| IEC, Schuko, NEMA, South Africa, UK | |||||
| Transfer time | Main to BAT | 0 | |||
| INV to BYP | 4ms | ||||
| Crest factor | 3:1 | ||||
| Efficiency (normal mod e) | Up to 95.0% | Up to 95.5% | |||
| Noise (1 meter ) | 45dB@>70% load or >6A charge | 50dB@>70% load or >6A charge | 50dB@>70% load or >6A charge | ||
| Overload | Normal | 102%~110%: 30mins, 110%~125%:10mins, 125%~150% : 30 seconds | |||
| mode | 102%~110%: 1min, 110%~125%: 10 seconds, 125%~150%:5 seconds | ||||
| Bypass mode | <130%: long time, 130%~150%:10mins , 150%~180%:5 seconds | ||||
| Battery | Model | 12.8Vdc/9AH for standard model | |||
| Quantity | 2/3 | 4/6 | 6/8 | ||
| Max charging | 1-4A(optional) | 1-4A(optional) | 1-4A(optional) | ||
| Rate voltage | 25.6VDC/38.4VDC | 51.2VDC/76.8VDC | 76.8VDC/102.4VDC | ||
| Standard | EPO, RS232 | ||||
| Option | SNMP card, AS400, USB, RS485, Air filter | ||||
| Dimension ,W*D*H(mm) | 144*350*223 | 190*400*328 | 190*400*328 | ||
| Weight (kg) | 16.6/19.1 | 21.5/26.7 | 26.7/31.5 | ||