1~3kVA 1P/1P, online double conversion
1~3kVA 1P/1P, online double conversion








| Rate Power | 1kVA/1kW | 1kVA/1kW | 2kVA/2kW | 2kVA/2kW | 3kVA/3kW | 3kVA/3kW | ||
| Cold start | Default output 50/60Hz | |||||||
| Input voltage range | 110~300VAC;100% load@176VAC~276VAC , 100%~ 50% power derating@110VAC~176VAC , 50% load@276VAC~300VAC | |||||||
| Input power factor | ≥0.99 | |||||||
| Frequency range | 50/60±5Hz(default),±3Hz(s ettable) | |||||||
| Output power factor | 1.0 | |||||||
| Output | Rate voltage | 208VAC/220VAC/230VAC/240VAC | ||||||
| Load response | ≤5% (0% - 100% -0% step load) | |||||||
| Recovery time | ≤40ms (0% - 100% -0% step load) | |||||||
| Output THDu | ≤2% , Linear load ; ≤ 5% non-linear load accordi ng to IEC62040-3 | |||||||
| Socket(option) | IEC, Schuko, NEMA, South Africa, UK | |||||||
| Transfer time | Main to BAT | 0 | ||||||
| INV to BYP | 4ms | |||||||
| Efficiency (normal mod e) | Up to 95.0% | Up to 95.5% | ||||||
| Noise (1 meter) | 45dB@>70% load or >6A charge | 50dB@>70% load or >6A charge | 50dB@>70% load or >6A charge | |||||
| Overload | Normal | 102%~110%: 30mins , 110%~125%:10mins , 125%~ 150%: 30 seconds | ||||||
| mode | 102%~110%: 1min , 110%~125%: 10 seconds , 125%~150%:5 seconds | |||||||
| Bypass mode | <130%: long time , 130%~150%:10mins , 150%~180%:5 seconds | |||||||
| Battery | Model | 12.8VDC/9Ah | 50Ah/100Ah | 12.8VDC/9Ah | 50Ah/100Ah | 12.8VDC/9Ah | 50Ah/100Ah | |
| Quantity | Depend on external battery | Depend on external battery | Depend on external battery | |||||
| Max charging | 2/3 | 4/6 | 6 | |||||
| Rate voltage | 1-4A(optional) | 1-12A(optional) | 1-4A(optional) | 1-12A(optional) | 1-4A(optional) | 1-12A(optional) | ||
| 25.6VDC/38.4VDC | 51.2VDC/76.8VDC | 76.8VDC/102.4VDC | ||||||
| Standard | EPO, RS232 | |||||||
| Option | SNMP card,AS400, USB, RS485, Air filter | |||||||
| Dimension ,W*D*H(mm) | 440*440*86 | 440*580*86 | 440*580*86 | |||||
| Weight (kg) | 16.5/19 | 9.5 | 22.6/27.5 | 9.7 | 28 | 10 | ||