Home > Products > UPS > 380V > Modular UPS > ACM Series 50~600kVA Modular UPS

ACM Series 50~600kVA Modular UPS

Power range

50~600 kVA

Operation

3P/3P, Online double conversion

Characteristics

  • Fully digital control, flexible and robust.
  • 7/10 inch touch LCD , with IoT functions .
  • High reliability and environmen tal adaptability, with protection of components level.
  • Supports battery connection wit hout Neutral.
  • Minimal footprint , standard width of 600 mm , depth of all models only 750 mm .

Applications

Government

Government

Finance

Finance

IT

IT

Education

Education

Transportation

Transportation

Broadcasting

Broadcasting

Medical

Medical

Energy

Energy

Data Parameters

Rate Power200kVA300kVA400kVA500kVA600kVA
Main
input
Input3P5W (3P+N+PE)
Rate Voltage380/400/415VAC(L-L);220/230/24 0VAC(L-N)
Rate Freq.50/60Hz
Input PF>0.99
Current distortionTHDi<2%
Voltage range304 478VAC(L-L)full load ; 304 228VAC (L-L) power derate from 100% to 50%
Freq. range40-70Hz
BatteryRate voltage±240VDC(default 40 PCS,30-50 PCS, selceted)
Charging capacityMax. 20%*Pout
Charging accuracy±1%
BypassRate voltage380/400/415 VAC (L-L);220/23 0/240 VAC (L-N)
Voltage rangeRange: -40%- +25% , Settable, default -20% +15%
Overload< 110%, long time operation
110%< load<125%, 10 mins
125%<load<150%,1 min
InverterRate voltage380/400/415VAC(L-L);220/230/24 0VAC(L-N)
Rate Freq.50/60Hz
Output PF1
Voltage accuracy±1.0%
Output THDu<1%(linear load),<5% (non-linea r load according to IEC 62040-3)
Overload110%,1 hour ; 125%,10 mins ; 1 50%,1 min ; >150%,200ms
Frequency accuracy0.1%
Synchronize windowSettable , ±0.5Hz-±5Hz , default ±3Hz
Slew rateSettable , 0.5Hz/S-3Hz/S , default 0.5Hz/S
Crest factor3:1
Phase Accuracy120°±0.5°
EnvironmentEfficiencyUp to 96.5%
DisplayLED + 7 inch touch LCDLED + 10 inch touch LCD
Certification- SafetyIEC62040-1, IEC60950-1
Certification- EMS IEC62040-2 ; IEC61000-4-2(ESD) ; IEC61000-4-3(RS) ; IEC61000-4-4 (EFT) ; I EC61000-4-5 (Surge)
Certification- Pref.IEC62040-3
ConfigurationUSB, RS232, RS485, Dry contact, Cold start, Air filter
OptionSNMP card AS400 card Parallel kit SPD Top air outlet
Environment0-40 ℃ (operation) ; -25 ℃ ~70 ℃ (storage) ; 0-95% (Humidity, non-condensing )
Noise(dB)(1 meter)72dB @ 100% load, 69dB @ 45% load
Dimension

Cabinet(W*D*H)mm

600*750*1600600*750*2000600*1000*20001200*850*2000
Module(W*D*H)mm440*475*140
Weight(kg)Cabinet170220320450
Module23
Power Module rated capacity50KW