ACwatt ACT-LV Series 10–40kVA Three-Phase Tower UPS provides online double-conversion power protection for 200/208/220V systems in branch server rooms, commercial IT facilities and campus networks.
Integrated battery options: Internal-battery models accommodate 12V/9Ah batteries in modular strips. Optional full-metal strips support configurations of up to 16 strips, depending on the selected model.
Full rated output: Available in 10, 20, 30 and 40kVA ratings with output power factor 1.0 and ±1% output voltage accuracy.
Model-specific efficiency: Efficiency reaches up to 94.5% for 10kVA, 95.5% for 20kVA and 94% for 30/40kVA models. Input power factor exceeds 0.99.
Monitoring and communication: A 7-inch touch LCD, USB, RS232, RS485 and dry contacts support local operation and system integration. SNMP and AS400 cards are optional.
Internal- and external-battery versions have different cabinet dimensions and weights. Battery supply, strip quantity and backup time depend on the selected configuration and connected load.




| Internal-Battery Model | TT010EB-LV-80P | TT020EB-LV-80P | TT030B-LV-160P | TT040B-LV-160P | |
|---|---|---|---|---|---|
| External-Battery Model | TT010EL-LV | TT020EL-LV | TT030L-LV | TT040L-LV | |
| Rated Power | 10kVA | 20kVA | 30kVA | 40kVA | |
| Input | Wiring | 3P5W (3P + N + PE) | |||
| Rated Voltage | 200/208/220VAC (L-L) | ||||
| Frequency | 50/60Hz; input range: 40–70Hz | ||||
| Power Factor | >0.99 | ||||
| Current Distortion | THDi <2.2% | THDi <3% | |||
| Voltage Range | 167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50% | ||||
| Battery | Rated DC Voltage | ±120VDC | |||
| Internal Configuration | 12VDC/9Ah batteries in modular battery strips | ||||
| External Configuration | 20 batteries by default; 20–24 selectable, depending on the external battery system | ||||
| Maximum Charging Capacity | 50% of Pout (internal and external versions) | 20% of Pout (internal and external versions) | |||
| Charging Accuracy | ±1% | ||||
| Bypass | Rated Voltage | 200/208/220VAC (L-L) | |||
| Voltage Window | Adjustable: −40% to +25%; default: −20% to +15% | ||||
| Frequency | 50/60Hz; selectable window: ±1Hz, ±3Hz or ±5Hz | ||||
| Output | Voltage / Frequency | 200/208/220VAC (L-L), 50/60Hz | |||
| Power Factor | 1.0 | ||||
| Voltage Accuracy | ±1.0% | ||||
| Voltage Distortion | THDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3 | ||||
| Inverter Overload | 110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms | ||||
| Frequency Accuracy | 0.1% | ||||
| System | Efficiency | Up to 94.5% | Up to 95.5% | Up to 94% | |
| Display | LED + 7-inch touch LCD | ||||
| Standard Features | USB, RS232, RS485, dry contacts, air filter, cold start, Ethernet | USB, RS232, RS485, dry contacts, air filter | |||
| Options | SNMP card, AS400 card, parallel kit | SNMP card, AS400 card, parallel kit, cold start | |||
| Environment | Operating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing | ||||
| Dimensions (W × D × H) | Internal-Battery Version | 400 × 861 × 783mm | 500 × 865 × 1250mm | ||
| External-Battery Version | 250 × 745 × 556mm | 250 × 728 × 650mm | |||
| Weight | Internal Version (Excluding Batteries) | 67kg | 68kg | 85kg | 87kg |
| External Version | 30.8kg | 31.8kg | 66kg | 72kg | |