ACwatt ACT-LV Series 10–30kVA Rack UPS provides online double-conversion power protection for 200/208/220VAC line-to-line three-phase systems in server racks, edge IT installations and network equipment rooms.
Rack or tower installation: Supports mounting in a 19-inch rack or installation as a tower UPS. The 10/15kVA models occupy 3U, the 20kVA model 4U and the 30kVA model 7U.
Power quality: Available in 10, 15, 20 and 30kVA ratings with output power factor 1.0, input power factor >0.99 and ±1% output voltage accuracy.
Flexible phase configuration: The series supports 3P/3P, 3P/1P and 1P/1P configurations. Voltage, wiring and available capacity must be matched to the selected operating mode.
Monitoring and communication: A 7-inch touch LCD, USB, RS232, RS485 and dry contacts support local monitoring and system integration. SNMP and AS400 cards are optional.
The specifications below describe the three-phase configuration. Confirm rack depth, mounting accessories, phase configuration and battery requirements before installation. Backup time depends on battery capacity and load.




| Model | TT010LR-LV | TT015LR-LV | TT020LR-LV | TT030LR-LV | |
|---|---|---|---|---|---|
| Rated Power | 10kVA | 15kVA | 20kVA | 30kVA | |
| Input | Wiring | 3P5W (3P + N + PE) | |||
| Rated Voltage | 200/208/220VAC (L-L) | ||||
| Frequency | 50/60Hz; input range: 40–70Hz | ||||
| Power Factor | >0.99 | ||||
| Current Distortion | THDi <3% | ||||
| Voltage Range | 167–260VAC at full load; from 167V down to 125V, power derates from 100% to 50% | ||||
| Battery | Rated DC Voltage | ±120VDC with default 20 batteries; 20–24 batteries selectable | |||
| Charging Capacity | Maximum 20% of Pout | ||||
| Charging Accuracy | ±1% | ||||
| Bypass | Rated Voltage | 200/208/220VAC (L-L) | |||
| Voltage Window | Adjustable: −40% to +25%; default: −20% to +15% | ||||
| Frequency | 50/60Hz; selectable window: ±1Hz, ±3Hz or ±5Hz | ||||
| Output | Voltage / Frequency | 200/208/220VAC (L-L), 50/60Hz | |||
| Power Factor | 1.0 | ||||
| Voltage Accuracy | ±1.0% | ||||
| Voltage Distortion | THDu <1% for linear load; <5% for nonlinear load according to IEC 62040-3 | ||||
| Inverter Overload | 110%: 1 hour; 125%: 10 minutes; 150%: 1 minute; >150%: 200ms | ||||
| Frequency Accuracy | 0.1% | ||||
| System | Efficiency | Up to 93% | |||
| Display | LED + 7-inch touch LCD | ||||
| Standard Interfaces | USB, RS232, RS485, dry contacts | ||||
| Options | SNMP card, AS400 card, parallel kit, air filter, cold start | ||||
| Protection | IP20 | ||||
| Environment | Operating: 0–40°C; storage: −25–70°C; humidity: 0–95%, non-condensing | ||||
| Mechanical | Rack Height | 3U | 4U | 7U | |
| Dimensions (W × D × H) | 440 × 906 × 130mm | 440 × 925 × 174mm | 440 × 945 × 308mm | ||
| Weight | 28kg | 29kg | 38kg | 60kg | |