ACD Series 6–20kVA Split-Phase Tower UPS

Product Overview

ACwatt ACD Series 6–20kVA Split-Phase Tower UPS provides online double-conversion power protection for compatible IT, commercial and control equipment requiring split-phase output.

Capacity options: Available in 6kVA/6kW, 10kVA/10kW and 20kVA/20kW models with an output power factor of 1.0.

Split-phase output: Supports 220/230/240V AC line-to-line output, with line-to-neutral connections for compatible loads. Select the voltage configuration to match the site supply and equipment.

Online protection: Full digital control and three-level topology deliver 0 ms mains-to-battery transfer, ±1% output voltage regulation and normal-mode efficiency of up to 92.5%.

Tower deployment: LED and LCD indication supports local operation. RS232, RS485 and EPO are standard, with optional SNMP, USB, AS400, parallel and maintenance bypass kits.

Confirm the line-to-line and line-to-neutral voltage combination, battery configuration and required backup time before ordering. Runtime depends on the connected load and selected batteries.

Applications

Edge IT

Edge IT

Heathcare

Heathcare

Education

Education

Commercial IT

Commercial IT

Server Rooms

Server Rooms

Data Parameters

ACD 6–20kVA Split-Phase Tower UPS Technical Specifications
ModelDD006B-TXDD010B-TXDD020L-TX
GeneralRated Power6kVA / 6kW10kVA / 10kW20kVA / 20kW
TopologySplit-phase, online double conversion
InputNominal Voltage220/230/240VAC, line-to-line
Voltage Range110–300VAC, line-to-line
Frequency Range50/60Hz ±5Hz
OutputLine-to-Line Voltage220/230/240VAC
Line-to-Neutral VoltageConfirm the required split-phase voltage combination when ordering
Power Factor1.0
Voltage Regulation±1%
Voltage THD≤2% linear load; ≤5% non-linear load
Crest Factor3:1
BatteryListed Battery Capacity7Ah9AhAccording to selected battery configuration
Battery Quantity16–20, configuration-dependent
Rated DC Voltage192VDC default, configurable
Maximum Charging Current1A
SystemMains-to-Battery Transfer0ms
Inverter-to-Bypass Transfer2ms
Normal-Mode EfficiencyUp to 92.5%
ECO-Mode EfficiencyUp to 96.5%
Normal-Mode Overload110%: 10min; 130%: 1min; 150%: 30s, then transfer to bypass
DisplayLED + LCD
InterfacesStandardRS232, RS485, EPO; cold-start function
OptionsAS400, SNMP card, USB, parallel kit, maintenance bypass kit
MechanicalW × D × H (mm)250 × 734 × 596350 × 576 × 704
Listed Weight (kg)85110

Battery supply, runtime and final configuration are subject to the selected model and project requirements. Normal-mode and ECO-mode efficiency figures refer to different operating modes.