1P/1P, online double conversion Characteristics 1~3kVA
1P/1P, online double conversion Characteristics 1~3kVA








| Rate Power | 1kVA/1kW | 2kVA/2kW | 3kVA/3kW | ||||
| Cold start | Default output 50/60Hz | ||||||
| Input voltage range | 50 ~ 150VAC ; 100% load@>90VAC ; 70% load@>70VAC ; 40% load@>50VAC | ||||||
| Input power factor | ≥0.99 | ||||||
| Frequency range | 50/60±5Hz(default), ±3Hz(s ettable) | ||||||
| Output power factor | 1.0 | ||||||
| Output | Rate voltage | 100/110/115/120VAC | |||||
| Load response | ≤5% (0% - 100% -0%) | ||||||
| Recovery time | ≤40ms (0% - 100% -0%) | ||||||
| Output THDu | ≤2% , Linear load ; ≤ 5% non-linear load accordi ng to IEC62040-3 | ||||||
| Transfer time | Main to BAT | 0 | |||||
| INV to BYP | 4ms | ||||||
| Crest factor | 3:1 | ||||||
| Efficiency (normal mod e) | Up to 94.5% | ||||||
| Noise (1 meter ) | <45dB | <50dB | |||||
| Overload | Normal | 102%~110%: 10mins, 111%~130% :1mins, 131%~150%: 30 seconds | |||||
| mode | <110%: 1min, >110%:5 seconds | ||||||
| Battery | Model | 12VDC/9Ah | |||||
| Quantity | 2 | 4 | 6 | ||||
| Max charging | Standard:1A default, Long backup: 3A default, 6A settable. 12A max | ||||||
| Rate voltage | 24VDC | 48VDC | 72VDC | ||||
| Standard | EPO, RS232 | ||||||
| Option | SNMP card, AS400, USB, RS485, Air filter | ||||||
| Dimension ,W*D*H(mm) | 144*355*226 | 191*400*328 | 144*398*223 | 191*400*328 | 144*398*223 | ||
| Weight (kg) | 16.6 | 5 | 21.5 | 7 | 26.7 | 7 | |