Home > Products > UPS > 480 / 208V > Single phase UPS > ACS-LV Series 4-12 kVA Single phase UPS

ACS-LV Series 4-12 kVA Single phase UPS

Product Overview

4–12kVA Single Phase Intelligent UPS (208V) provides reliable power protection for IT equipment, network systems and other critical loads requiring 208V power.

Flexible capacity: Covers 4–12kVAto support different load requirements and deployment scenarios.

Flexible installation: Tower and rack-oriented configurations provide greater flexibility for equipment rooms and IT environments.

208V power protection: Designed for applications requiring stable 208V UPS powerfor business-critical equipment.

Configuration Note: Final UPS capacity, installation method and battery configuration depend on load and project requirements.

Applications

Government

Government

Finance

Finance

Broadcasting

Broadcasting

Medical

Medical

Energy

Energy

Data Parameters

ACS Series LV 4-12kVA Single Phase UPS Technical Specifications for ACS004LVB, ACS004LV, ACS006LVB, ACS006LV and ACS012LV.
ModelACS004LVBACS004LVACS006LVBACS006LVACS012LV
InputCold StartYes; default output frequency 60Hz, settable
Acceptable Input Voltage60-155VAC
Input Voltage / Load100% load @ >105VAC;
90% load @ >95VAC;
75% load @ >80VAC;
50% load @ >60VAC
PhaseSingle phase input, single phase output
Transfer Voltage Range110VAC / 115VAC / 120VAC / 127VAC
Line Low Transfer / Recovery60VAC / 86VAC
Line High Transfer / Recovery160VAC / 155VAC
Input Current34A / 120V39A / 120V50A / 120V54A / 120V108A / 120V
Input Power Factor≥0.99
Input Current Distortion<4%
Input Frequency Range40-70Hz
OutputFrequency AdaptableSettable
Rated Power4kVA4kVA6kVA6kVA12kVA
Rated Active Power4kW4kW4kW4kW12kW
Waveform (Battery Mode)Pure Sine Wave
Nominal Output Voltage110VAC / 115VAC / 120VAC / 127VAC;
PF = 0.9 @ 110VAC / 115VAC
Voltage Regulation±1%
Output THD≤1% THD, linear load;
≤5% THD, non-linear load
Synchronization Range±5Hz default, settable
Battery Mode Frequency50 ±0.1Hz default
Line Mode to Battery Mode0ms
Inverter to Bypass0ms
Normal Mode Efficiency91.5% @ 100% load; 92% @ 60% load
ECO Mode Efficiency98%
Noise (1m Away)<58dB<60dB
Crest Ratio3:1
OverloadInverter Mode105%-110%: transfer to bypass after 10 min;
111%-125%: transfer to bypass after 1 min;
126%-150%: transfer to bypass after 30 sec
Bypass Mode<125%: continuous operation;
126%-130%: shutdown in 5 min;
131%-150%: shutdown in 1 min;
>150%: shutdown in 200ms
BatteryBattery Type12VDC / 7AhExternal Battery12VDC / 9AhExternal BatteryExternal Battery
Battery Quantity16 pcs default12-16 pcs, settable16 pcs default12-16 pcs, settable12-16 pcs, settable
DC Voltage192VDC default, settable
Backup Time5 min @ 4kWDepends on external battery capacity5 min @ 6kWDepends on external battery capacityDepends on external battery capacity
Maximum Charging Current1A, settable8A max., settable1A, settable8A max., settable8A max., settable
Float Charging Voltage2.25V/cell default, settable
Boost Charging Voltage2.25V/cell default, settable
Charging Time8h recharge to 90%Depends on external battery capacity8h recharge to 90%Depends on external battery capacityDepends on external battery capacity
SystemLeakage Current<3mA
DisplayLED + LCD
Smart RS232Standard cable, supports ACview Monitor Software
EPONormally Closed
RS485Standard
SNMPOptional, Web Browser
Dry ContactOptional Intelligent Kit
Parallel OperationUp to 4 units
12A ChargerOptional, digitally controlled
USBB-type USB port
SNMP KitOptional, pluggable type
MechanicalDimension (W × D × H) mm190 × 495 × 550190 × 495 × 338190 × 495 × 550190 × 495 × 338190 × 495 × 550
InstallationTower
ColorBlack (default)