50–600kVA Modular UPS is a scalable online double-conversion power system designed for telecommunications, data processing, industrial control, and other critical loads.
Scalable capacity: 50kVA power modules support system expansion from 50kVA to 600kVA, with flexible capacity and redundancy configurations.
Wide input range: A -40% to +25% input-voltage range, input power factor of 0.99, and THDi of 2% support stable operation.
High efficiency: Online double-conversion efficiency reaches up to 96%, while ECO mode reaches 99%.
Flexible integration: Supports external batteries, RS232, RS485, USB, dry contacts, EPO, optional SNMP monitoring, and optional parallel communication.
Final configuration depends on load capacity, redundancy, battery backup time, cabinet type, cable entry, and project requirements.








| Cabinet and Module Configuration | ||||
| Platform | Maximum Capacity | Dimensions (W × D × H) | Net Weight | Configuration |
|---|---|---|---|---|
| 4-Slot Cabinet | 200kVA | 600 × 750 × 1600 mm | 170 kg | Up to 4 modules |
| 6-Slot Cabinet | 300kVA | 600 × 750 × 2000 mm | 220 kg | Up to 6 modules |
| 4/6-Slot Four-Switch Cabinet | 200 / 300kVA | 600 × 850 × 2000 mm | 300 / 346 kg | Integrated four-switch design |
| 8-Slot Cabinet | 400kVA | 600 × 1000 × 2000 mm | 320 kg | Up to 8 modules |
| 10/12-Slot Cabinet | 500 / 600kVA | 1200 × 750 × 2000 mm or 1200 × 850 × 2000 mm | 442 / 450 kg | Up to 10 or 12 modules |
| 50kVA Power Module | 50kVA | 440 × 475 × 140 mm | 23 kg | Modular power unit |
| AC Input | |
| Rated Input Voltage | 380 / 400 / 415 Vac, three-phase four-wire |
| Input Voltage Range | -40% to +25% |
| Rated Frequency | 50 / 60 Hz |
| Input Frequency Range | 40–70 Hz |
| Input Power Factor | 0.99 at full load |
| Input Current Distortion | THDi 2% |
| AC Output | |
| Rated Capacity | 50–600kVA |
| Rated Output Voltage | 380 / 400 / 415 Vac, three-phase four-wire |
| Rated Frequency | 50 / 60 Hz |
| Output Voltage Distortion | <1% with linear load; <3% with non-linear load |
| Voltage Stability | ±1% balanced load; ±1.5% at 100% unbalanced load |
| Transient Voltage Response | ±5% |
| Neutral Current Capability | 170% |
| Overload Capability | 110% for 1 hour; 125% for 10 minutes; 150% for 1 minute |
| Short-Circuit Current Limitation | 300% for 200 ms |
| Battery and Charger | |
| Battery System | External battery system |
| Battery Bus Voltage | Nominal ±192 to ±240 Vdc |
| Nominal Lead-Acid Configuration | 40 × 12V battery blocks per string |
| Float Charge Voltage | 2.25 V/cell; adjustable from 2.20 to 2.35 V/cell |
| Boost Charge Voltage | 2.40 V/cell; adjustable from 2.30 to 2.45 V/cell |
| Temperature Compensation | -3.0 mV/°C/cell; adjustable from 0 to -5.0 |
| Battery Charging Power | 10% default; adjustable from 1% to 20% of UPS capacity |
| Bypass and Efficiency | |
| Rated Bypass Voltage | 380 / 400 / 415 Vac, three-phase four-wire |
| Synchronized Transfer Time | 0 ms |
| Bypass Voltage Tolerance | Upper: +10%, +15%, +20% or +25%; lower: -10%, -20%, -30% or -40% |
| Bypass Frequency Tolerance | ±2.5%, ±5%, ±10% or ±20% |
| Online Double-Conversion Efficiency | Up to 96% |
| ECO Mode Efficiency | Up to 99% |
| Environment, Protection and Communication | |
| Operating Temperature | 0–40°C |
| Relative Humidity | 0–95%, non-condensing |
| Operating Altitude | Up to 3000 m without derating |
| Acoustic Noise | 61 dB at 1 m for the power module |
| Protection Level | IP20 |
| Standard Communication | RS232, RS485 and USB |
| Optional Communication | SNMP intelligent card and parallel communication ports |
| Monitoring Interfaces | EPO, generator signal, battery breaker status, battery and ambient temperature, battery-low alarm, general alarm, and utility-failure alarm |